Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02086
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/19/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM02086 DENIED 5/19/04 1. Provide accent lighting fixture schedule and cut sheet. 2. Provide Panel and circuit number for all electrical loads, such as accent lighting, pendant fixtures, and quad receptacles. 3. Provide panel load calculations. |
05/19/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
05/19/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
05/19/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/20/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
05/21/2004 | EGRANT1 | WWM | REVIEW | Passed | |
05/21/2004 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved |