Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM02077
Parcel: 14042075B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02077
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/13/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/14/2004 GERRY KOZIOL WWM REVIEW Denied wwm needs iwc approval of dental x-ray
06/01/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. In General Note D on Sheet E2, please change the reference to NEC Article 660 to NEC Article 517. The scope of Article 660 is nonmedical and nondental applications.
2. Provide power to EF-2, located in the Dark Room.
3. Provide disconnects to X-Ray machines on Ckts P1-13, P1-19, P1-25, P1-31, and P1-37, or justify otherwise.
4. The #6 conductor on the line side of the new service disconnect constitutes a redundant path to ground. Please delete.
5. The #1 feeder to new Panel P1, of ampacity 130A, will not carry the 158A load, and is not adequately protected by the 200A fuse. Please correct New Tenant Riser Diagram, Sheet E3, on notation above and to the left of Panel P1.
6. Please specify each series-rated combination of overcurrent protective devices, clearly identifying line side device, load side device, line side rating, and load side rating.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/02/2004 TAMI ACHONG OUT TO CUSTOMER Completed
06/02/2004 ANGIE SHOFFSTALL REJECT SHELF Completed