Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM02077
Parcel: 14042075B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02077
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/10/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water pressure calculations to show how the water piping was sized.
2. Provide riser diagrams for the water and the waste piping systems.
3. Revise the water fixture calculation for P-5.
4. State the mounting height of the water heater.
5. Revise hot water return piping on the water heater schematic.
05/10/2004 DAN CASTRO ZONING REVIEW Approved
05/10/2004 ROBERT SHERRY WATER REVIEW Approved
05/10/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise total amount of outside air per Section 403.3.2, IMC 2000.
05/11/2004 ANY BUILDING-COMMERCIAL REVIEW Approved
05/11/2004 JIM EGAN FIRE REVIEW Approved
05/11/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/13/2004 EGRANT1 WWM REVIEW Needs Review