Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02077
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 05/10/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water pressure calculations to show how the water piping was sized. 2. Provide riser diagrams for the water and the waste piping systems. 3. Revise the water fixture calculation for P-5. 4. State the mounting height of the water heater. 5. Revise hot water return piping on the water heater schematic. |
| 05/10/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 05/10/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/10/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise total amount of outside air per Section 403.3.2, IMC 2000. |
| 05/11/2004 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/11/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/11/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/13/2004 | EGRANT1 | WWM | REVIEW | Needs Review |