Permit Number: T04CM02072
Parcel: 13824022H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02072
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2004 MELISSA POULIN WWM REVIEW Approved
05/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM02072 DENIED 5/13/04
1. Note 7 indicates that track lights are on Circuit A-2. According to the panel schedule this circuit only has the corridor can lights.
2. Note 8 indicates that track lights are on Circuit A-4. Panel schedule does not include 25% for continuos load, such as lighting. Please do so per NEC 215-2 (a).
3. Panel has almost 400A on each of 3 phases. This exceeds the 150A bus capacity. Please clarify.
05/14/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/14/2004 TAMI ACHONG OUT TO CUSTOMER Completed