Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02072
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 05/14/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM02072 DENIED 5/13/04 1. Note 7 indicates that track lights are on Circuit A-2. According to the panel schedule this circuit only has the corridor can lights. 2. Note 8 indicates that track lights are on Circuit A-4. Panel schedule does not include 25% for continuos load, such as lighting. Please do so per NEC 215-2 (a). 3. Panel has almost 400A on each of 3 phases. This exceeds the 150A bus capacity. Please clarify. |
| 05/14/2004 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/14/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |