Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02055
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide a detail to show how the integrity of the firewall separating the units is being maintained with the exhaust ducts from the first floor rest rooms located inside the wall. Show how the duct is to exit the wall and terminate on the roof. Reference Section 705, IBC 2003. 2. Comment not addressed. The heating and cooling system design load calculations have not been provided. Reference Section 106.3.1, IMC 2000, and Section 503.3, IECC 1998 with local amendments. 3. Revise sheet 5b (Roof Framing) to coordinated with the changes that were made to sheet 8, providing adequate maintenance access and operational clearance for the heat pumps. Reference Sections 304.1 and 306.1, IMC 2000. 4. Comment not addressed. Coordinate the changes to the HVAC equipment with the electrical design (e.g. heat strip). (Submit a copy of the approved electrical plan with the revised plan.) |
| 05/09/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The provided cut sheet shows that the specified water heater has an input of 50,000 BTUH, not 40,000 BTUH as shown on sheet 7 (plumbing notes and detail 3); please revise. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/12/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 05/12/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |