Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02055
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The water calculations (based on Appendix A, UPC 1994) shown on sheet 7 neglect the minimum required water pressure (15 PSI). Resize the water piping as required. 2. The shutoff valve shown on detail 4/sheet 7 is not located immediately ahead of the water heater. The valve should be located after any branch piping that serves other areas. Revise the water heater installation detail to show the required shut off valve. Reference Section 605.5, UPC 1994. 3. Coordinate the location of the expansion tank shown on the water isometric with the water heater installation detail. The expansion tank shall be located immediately after the cold water shutoff valve for the water heater. Reference Section 608.3, UPC 1994 with AZ State amendments. 4. The specified water heater is designed with an atmospheric vent. As such, the vent must terminate above the roof. Reference Section 517.1, UPC 1994. |
| 04/12/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. SHOW the route, cleanouts, and termination of the dryer exhaust ducts. Provide listing information to show that a 6" duct is an appropriate size for an exhaust duct. The exhaust ducts for the dryers shall terminate outside the building; revise the mechanical note on sheet 8 to indicate how the clothes dryer exhaust is to comply with the 2000 IMC. Reference Sections 106.3.1 and 504, IMC 2000. 2. Comment not addressed. Provide a detail to show how the integrity of the firewall separating the units is being maintained with the exhaust ducts from the first floor rest rooms located inside the wall. Show how the duct is to exit the wall and terminate on the roof. Reference Section 705, IBC 2003. 3. The heating and cooling system design load calculations have not been provided. Reference Section 106.3.1, IMC 2000, and Section 503.3, IECC 1998 with local amendments. 4. Provide adequate maintenance access and operational clearance for the heat pumps per the manufacturer's installation instructions. Revise the drawing to show the proper amount of clearance. Reference Sections 304.1 and 306.1, IMC 2000. 5. Coordinate the changes to the HVAC equipment with the electrical design (e.g. heat strip). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/13/2005 | DELMA ROBEY | OUT TO CUSTOMER | Completed |