Permit Number: T04CM02049
Parcel: 129140250

Address:
2635 S EUCLID AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02049
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2004 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM02049

6/7/04 2635 S. EUCLID

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN:

1. PLEASE INDICATE A ONE HOUR FIRE WALL FOR THE WALL THAT IS PARALLEL TO THE PROPERTY LINE AND LESS THAN 3 FEET FROM THE PROPERTY LINE. THIS ONE HOUR WALL IS REQUIRED AND CAN CONTAIN ONLY WINDOWS THAT ARE LISTED FOR ONE HOUR FIRE RESISTIVE INSTALLATIONS. PLEASE INDICATE IT'S LOCATION ON THE SITE PLAN.

FLOOR PLANS:

1. THE EXISTING CARPORT IS A GARAGE (NOT OPEN ON TWO SIDES, R309.4) AND GARAGES CAN'T HAVE OPENINGS INTO SLEEPING ROOMS. SEE R309.1 . A SEPARATION IS REQUIRED BETWEEN THE GARAGE AND THE DWELLING WITH ½" GYPSUM BOARD. HOW DOES THE WINDOW COMPLY WITH R 309.2 ? THE WINDOW IS NOT PERMITTED.

1. HOW DOES THE BEDROOM'S EGRESS COMPLY WITH R310 IF THE WINDOW IS OMITTED? THE WINDOW IS NOT PERMITTED IN A GARAGE OR LESS THAN 3' FROM THE PROPERTY LINE. A LISTED FIRE RATED WINDOW WILL NOT PERMIT EGRESS FROM THE BEDROOM. HOW WILL EGRESS BE PROVIDED?

2. IS AN EXISTING WINDOW BEING CLOSED IN THE EXISTING BATH ROOM? WILL AN VENT FAN BE REQUIRED? THIS WINDOW IS NOT PERMITTED IN A GARAGE. CLOSE THE WINDOW. IS A VENTILATION FAN EXISTING OR WILL ONE HAVE TO BE ADDED?

3. HOW IS EGRESS ACHIEVED FROM THE EXISTING BEDROOM? SEE R310. HOW IS LIGHT AND VENTILATION PROVIDED? SEE R303.HOW IS LIGHT AND VENTILATION BEING PROVIDED IN THE NOW "NEW SITTING ROOM"? SEE R303.

8. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2. PLEASE NOTE THIS ON THE PLANS.



STRUCTURAL PLANS:

1. JUSTIFY THE EXISTING RAFTERS AND BEAMS ABILITY TO SOPPORT THE ADDED ROOF'S WEIGHT. IF THE OVER FRAME IS NOT TO BE DONE, PLEASE REMOVE IT FROM THE PLANS. PROVIDE A VENTILATED CRICKET .

2. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE
MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF
SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF
LOWER TRUSSES. IF THE OVER FRAME IS TO BE DELETED, PLEASE DELETE IT FROM THE PLANS AND PROVIDE A VENTED CRICKET.

SECTIONS - DETAILS - MISC. NOTES:

1. PROVIDE A DETAIL OR DESCRIBE THE ONE HOUR FIRE WALL. THE 5/8" TYPE "X" G.W.B. IS REQUIRED ON BOTH SIDES OF THE FIREWALL. THE WINDOW SHOWN IS NOT PERMITTED IN A FIRE WALL. SEE X / 2 .

2. X / 2 ; THE FIRE PROTECTION IS REQUIRED TO EXTEND TO THE ROOF DECK. PLEASE EXTEND THE 5/8" G.W.B. TO THE ROOF .

4. A / 3 ; THE FIRE RATING IS REQUIRED TO EXTEND TO THE ROOF DECK. PLEASE ILLUSTRATE @ A/3.

PLUMBING PLANS:

1. PROVIDE COMBUSTION AIR FOR THE WATER HEATER. IF THE WATER HEATER ISN'T ENCLOSED, NOTE ON THE PLANS THAT THE WATER HEATER IS TO BE LISTED AS APPROVED FOR EXTERIOR INSTALLATION.

2. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. PLEASE NOTE ON THE PLANS OR PROVIDE PLUMBING NOTE 23 ON SHT. 6 .

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC. PLEASE NOTE ON THE PLANS OR PROVIDE ELECTRICAL NOTE 16 .



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110