Permit Number: T04CM02032
Parcel: Unknown

Address:
750 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02032
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2004 JIM EGAN FIRE REVIEW Denied Fire sprinklers required in basement.
05/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the terminaion of the T&P relief of the water heater.
2. Coordinate the waste and vent isometric with the plumbing plan.
3. Provide a riser diagram for the water piping.
05/07/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
05/07/2004 ROBERT SHERRY WATER REVIEW Approved
05/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation calculations.
05/14/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
05/14/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/20/2004 LLESNY1 WWM REVIEW Needs Review
05/20/2004 LLESNY1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2004 LISA LESNY OUT TO CUSTOMER Completed