Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T04CM02030
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 06/07/2004 | David Witt | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T04CM02030 6/8/04 322 E. TETON RD. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FLOOR PLANS: 1. SHEATHING, A ; THE HOLD DOWNS ARE REQUIRED TO PROVIDE A MINIMUM OF 1800# OF TENSILE STRENGTH. SEE R602.10.6 . THE PAHD 42 AT THE END STUD ADJACENT A CORNER IS LESS THAN 1800# . 2. NOTE #5 ; JUSTIFY THE 3/8" GYPSUM BOARD ON 24" OC FRAMING. SEE TABLE R702.3.5 . PLEASE REVISE THE DETAILS TO REFLECT FOOTNOTE D . 3. JUSTIFY THE SCREWS IN THE SHEAR PANELS. STRUCTURAL PLANS: 1. JUSTIFY THE ADEQUACY OF THE 8d NAILS CONNECTING THE OUTRIGGERS TO THE TRUSSES. 2. JUSTIFY THE ADEQUACY OF THE TRUSSES AFTER THE NOTCHING OF THE TOP CHORD OF THE TRUSSES FOR THE OUTRIGGERS. 3. THE TRUSS DEFERRED SUBMITTAL WILL HAVE TO BE SUBMITTED AND NOT WALKED THROUGH PLAN CHECK. 4. PROVIDE A LISTING FOR THE "HGUS26" JOIST HANGERS. I CAN'T FIND THEM IN SIMPSON. 5. THE HEADER SCHEDULE APPEARS TO BE UNDER SIZED. PLEASE JUSTIFY. 6. CLARIFY FRAMING NOTES 2 AND 10 . 7. FRAMING NOTE 5 SPECIFIES 16" OC STUDS BUT THE DETAILS SPECIFY 24" OC. PLEASE CO-ORDINATE. SECTIONS - DETAILS - MISC. NOTES: 1. SECTION A /7 ; SEE R905.2.2 FOR THE LIMITS ON THE SLOPE USED FOR ASPHALT SHINGLES AND THEN SPECIFH THE ROOFING FOR THE CRICKET BETWEEN THE UNITS. 2. 3 / 8 ; SPECIFY THE DISC ON THE PINS. 3. 4 / 8 ; THE DIMENSIONED WIDTH DIFFERS FROM THESTATED WIDTH. PLEASE CO-ORDINATE. 4. 4, 5 /8 ; PLEASE SPECIFY THE MINIMUM EMBEDMENT OF THE ANCHOR BOLTS INTO CONCRETE. 5. 6 , 7 / 8 ; JUSTIFY THE 16" SPACING OF THE 8d SHEAR CONNECTION OF THE SHEAR BLOCKS TO THE ROOF DECK. PLUMBING PLANS: 1. THE FIXTURE UNIT COUNT SHOULD BE IN ACCORD WITH THE UNIFORM PLUMBING CODE NOT THE I.R.C. 2. PLEASE CHECK THE WATER DISTRIBUTION SIZES AFTER THE WATER HEATERS USING THE U.P.C. MECHANICAL PLANS: 1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC AND NOT THE I.M.C.. 2. COMBUSTION AIR IS SIZED IN ACCORD WITH THE U.P.C. BUT THE SITE PLAN SHOWS NO GAS. IF THE WATER HEATER IS GAS, PROVIDE A GAS LINE; IF IT'S ELECTRIC, ADD IT TO THE ELECTRIC LOAD CALCULATIONS. ELECTRICAL PLANS: 1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC. THE N.E.C. DOESN'T APPLY. SEE THE SCOPE OF THE I.R.C. IN R101.2 . 2. PLEASE INCLUDE TWO 20 AMP CIRCUITS IN THE LOAD CALCULATIONS. SEE E3603.2 . 3. PLEASE VERIFY THE LOAD REQUIRED BY THE 4 TON A/C WITH HEAT STRIPS. 4. RISER DIAGRAM AND THE PLAN ; ONLY ONE ELECTRIC SERVICE IS PERMITTED FOR A DUPLEX. SEE E3501.2 . ALSO T.E.P. WILL GIVE ONLY ONE CABLE DROP. 5. A RECEPTACLE IS REQUIRED AT THE PENINSULAR COUNTER TOP. SEE E3801.4.3 . 6. THE RECEPTACLES AT THE KITCHEN COUNTER TOP APPEAR TO BE OVER SPACED. SEE E3801.4.1 . 7. A RECEPTACLE IS REQUIRED IN THE HALL. SEE E3801.10 . 8. TWO 20 AMP CIRCUITS ARE REQUIRED TO SERVE EACH KITCHEN. SEE E3603.2 . 9. PLEASE INCLUDE THE WATER HEATER IN THE LOAD CALCULATIONS. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/09/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |
| 06/09/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |