Permit Number: T04CM02023
Parcel: 11712032B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02023
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
05/05/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
05/06/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide manufacturer's model number and listing information for the sump basin and the sump pump.
2. Provide a check valve for the sump pump discharge.
3. Show that the existing 3" waste line is capable of accepting the discharge of the sump pump.
4. Clarify the material used for the pumped waste - Type M copper or DWV copper?
05/06/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/06/2004 ROBERT SHERRY WATER REVIEW Approved
05/06/2004 JIM EGAN FIRE REVIEW Approved
05/06/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/10/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
05/17/2004 DROBEY1 WWM REVIEW Needs Review