Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02023
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/05/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
05/05/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
05/06/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide manufacturer's model number and listing information for the sump basin and the sump pump. 2. Provide a check valve for the sump pump discharge. 3. Show that the existing 3" waste line is capable of accepting the discharge of the sump pump. 4. Clarify the material used for the pumped waste - Type M copper or DWV copper? |
05/06/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/06/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/06/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
05/06/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
05/10/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/17/2004 | DROBEY1 | WWM | REVIEW | Needs Review |