Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T04CM02014
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/01/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | A copy of the stamped approved site plan must be included in the submittal. |
06/02/2004 | GERRY KOZIOL | WWM | REVIEW | Passed | |
06/03/2004 | JIM EGAN | FIRE | REVIEW | Denied | 1. Fire sprinklers, fire standpipes, and fire pump to existing Courts building shall be in full service at all times that the building is occupied. 2. New fire sprinkler piping not sized, type of pipe not specified, and installation does not appear to be in accordance with NFPA 13 and NFPA 24. 3. Correctly label existing fire pump test header. 4. Fire sprinkler riser detail on Sheet P5.0 is incorrect and not acceptable. 5. Correctly indicate new/existing Standpipe piping, Fire Pump supply piping and Fire Sprinkler piping. |
06/03/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/08/2004 | DAVID RIVERA | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/09/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |