Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM02014
Parcel: 11716029A

Address:
103 E ALAMEDA ST

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T04CM02014
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2004 JIM TATE ENGINEERING REVIEW Approved A copy of the stamped approved site plan must be included in the submittal.
06/02/2004 GERRY KOZIOL WWM REVIEW Passed
06/03/2004 JIM EGAN FIRE REVIEW Denied 1. Fire sprinklers, fire standpipes, and fire pump to existing Courts building shall be in full service at all times that the building is occupied.
2. New fire sprinkler piping not sized, type of pipe not specified, and installation does not appear to be in accordance with NFPA 13 and NFPA 24.
3. Correctly label existing fire pump test header.
4. Fire sprinkler riser detail on Sheet P5.0 is incorrect and not acceptable.
5. Correctly indicate new/existing Standpipe piping, Fire Pump supply piping and Fire Sprinkler piping.
06/03/2004 ROBERT SHERRY WATER REVIEW Approved
06/08/2004 DAVID RIVERA ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2004 TAMI ACHONG OUT TO CUSTOMER Completed