Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Approved
07/20/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanouts for P5 located in Unit 5, second floor and for P6 and P3b, located in Unit 4, third floor. Reference Section 707.4, UPC 1994, as modified by the State of Arizona.
2. Provide a listing for the fireplace showing a gas capacity of 15 CFH. (shown variously as 15 CFH and 25 CFH)
3. Coordinate the gas piping to Unit 7 on the third floor. Sheet P2.2 shows two gas pipes feeding the space but sheet P2.3 only shows one gas pipe.
4. Provide size and listing for the air gap fitting shown in detail 1/P4.1 to verify that the air gap fitting and its drain line are capable of handling the discharge of the T&P valve on WH-1.
07/22/2004 GERRY KOZIOL WWM REVIEW Approved
07/23/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
07/28/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/29/2004 BETH GRANT OUT TO CUSTOMER Completed
07/29/2004 ANGIE SHOFFSTALL REJECT SHELF Completed