Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T04CM02010
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2004 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/20/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide cleanouts for P5 located in Unit 5, second floor and for P6 and P3b, located in Unit 4, third floor. Reference Section 707.4, UPC 1994, as modified by the State of Arizona. 2. Provide a listing for the fireplace showing a gas capacity of 15 CFH. (shown variously as 15 CFH and 25 CFH) 3. Coordinate the gas piping to Unit 7 on the third floor. Sheet P2.2 shows two gas pipes feeding the space but sheet P2.3 only shows one gas pipe. 4. Provide size and listing for the air gap fitting shown in detail 1/P4.1 to verify that the air gap fitting and its drain line are capable of handling the discharge of the T&P valve on WH-1. |
| 07/22/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/23/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/28/2004 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/29/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 07/29/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |