Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM02008
Parcel: 13623511A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM02008
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2004 GERRY KOZIOL WWM REVIEW Approved
06/09/2004 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM02008

6/11/04 3627 S. ALBERTA PL.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM
IF IT EXISTS.


FLOOR PLANS:

1. PLEASE INDICATE A BRACED WALL PANEL FOR THE WEST END OF THE NORTH FAMILY ROOM WALL. SEE R602.10.1 .

2. CLARIFY "CERAMIC TILE DECK AND WAINSCOT……." . IF THE DECK IS THE CEILING, PLEASE ADDRESS R702.4.2 .

STRUCTURAL PLANS:

1. PLEASE SPECIFY THE PORCH BEAM.

2. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA.

3. PLEASE SPECIFY THE POSTS.

SECTIONS - DETAILS - MISC. NOTES:

1. 1 / A1 ; PAHD-42 ISN'T LISTED AT 1800# ON END STUDS LESS THAN 8" FROM AN OUTSIDE CORNER. SEE R602.10.6 AND SIMPSON.

2. 1 / A1 ; ALTERNATE BRACED WALL PANELS REQUIRE ANCHOR BOLTS AT QUARTER POINTS. SEE R602.10.6 .

3. 2 / A1 ; CLARIFY "DYSET". IF IT'S AN EPOXY A SPECIAL INSPECTION FORM AUTHORIZING AN ENGINEER TO APPROVE THE EPOXY INSTALLATION IS REQUIRED.

4. 2 / A4 ; CLARIFY "2 X 4 KNEE BRACE AT RIDGE". THERE DOESN'T APPEAR TO BE A RIDGE.

5. 3 / A4 ; SPECIFY THE JOIST HANGER.

6. 3,4 / A4 ; WILL THE PORCH CEILING HAVE EXPOSED RAFTERS OR HAVE A GYPSUM BOARD CEILING?

7. 4 / A1 ; PROVIDE WEEP HOLES, FLASHING AND BRICK TIES. SEE R703.7 AND R703.8 .

8. 4 / A1 ; THE MINIMUM FOOTING WIDTH FOR A VENEERED FRAME WALL IS 19". SEE TABLE R403.1 .

9. 5 / A1 ; PLEASE REINFORCE THE PAD FOOTINGS IN BOTH DIRECTIONS.

10. 5 / A1 ; THE SIMPSON "PB" SERIES DOESN'T PROVIDE 1" CLEARANCE BETWEEN THE END GRAIN AND THE CONCRETE, SO A REDWOOD OR PRESSURE TREATED POST IS REQUIRED. SEE R323.1.4 . PLEASE CLARIFY "PB566".

11. 5 / A4 ; PLEASE CLARIFY THE 2X BLOCKING.

12. HOW DOES THE ½" GYP BOARD CEILING COMPLY WITH TABLE R702.3.5, FOOTNOTE d ?

13. A / A3 ; THIS SECTION APPEARS TO BE TAKEN THROUGH A PORCH POST. PLEASE REFERENCE 6 / A1 FOR THE POST BASE AND 7 / A1 AS "BEYOND" .

PLUMBING PLANS:

1. JUSTIFY THE EXISTING GAS PIPING SYSTEM'S ABILITY TO SUPPLY THE EXISTING GAS DEMAND AND THE PROPOSED GAS DEMAND OR TAKE THE PROPOSED GAS LINE BACK TO THE GAS METER.

ELECTRICAL PLANS:

1. PLEASE RENAME THE ELECTRICAL PLAN.


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2004 TAMI ACHONG OUT TO CUSTOMER Completed
06/15/2004 SUE REEVES REJECT SHELF Completed