Permit Number: T04CM01987
Parcel: 105102430

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01987
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2004 DAVID RIVERA ZONING REVIEW Approved
05/05/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise fixture schedule to reflect public fixture units for clothes washer.
2. The fixture schedule calls for 3/4" CW and HW connections for the clothes washer but the floor plan and detail 3/MP.1 show only 1/2" CW and HW supplying the unit. Please revise.
05/05/2004 JIM EGAN FIRE REVIEW Approved
05/05/2004 ROBERT SHERRY WATER REVIEW Approved
05/05/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the total ventilation being supplied to the project per section 403.3.2, IMC 2000. Show calculations for each rooftop unit.
05/06/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
05/14/2004 TACHONG1 WWM REVIEW Needs Review
05/14/2004 TACHONG1 ENGINEERING REVIEW Needs Review
05/14/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/14/2004 TAMI ACHONG OUT TO CUSTOMER Completed