Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01987
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/04/2004 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/05/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise fixture schedule to reflect public fixture units for clothes washer. 2. The fixture schedule calls for 3/4" CW and HW connections for the clothes washer but the floor plan and detail 3/MP.1 show only 1/2" CW and HW supplying the unit. Please revise. |
| 05/05/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/05/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/05/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the total ventilation being supplied to the project per section 403.3.2, IMC 2000. Show calculations for each rooftop unit. |
| 05/06/2004 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/14/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 05/14/2004 | TACHONG1 | ENGINEERING | REVIEW | Needs Review | |
| 05/14/2004 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/14/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |