Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM01956
Parcel: 12704245A

Address:
5033 E 5TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01956
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2004 JIM EGAN FIRE REVIEW Approved
05/06/2004 EGRANT1 WWM REVIEW Needs Review
05/06/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the plumbing floor plan to show the vent for the floor sink.
2. Include all gas appliances in the gas pipe sizing calculations. Revise pipe sizes as required.
05/06/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/06/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
05/06/2004 EGRANT1 WATER REVIEW Needs Review
05/06/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the temperature control for the project complies with section 309.1, IMC 2000.
2. Provide a Type I hood for the range. Revise the airflow to comply with Section 507.13.3, IMC 2000.
3. Provide listing information for the hood exhaust fan.
4. Provide details to show how the hood is to be supported. Include the weight of the hood on the plans. Reference Section 507.6, IMC 2000.
05/06/2004 NEAL SAUNDERS ELECTRICAL-COMMERCIAL REVIEW Approved
05/06/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved