| 05/20/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Correct total ventilation rate using Section 403.3.2, IMC 2000 for common ventilation systems. 2. Correct the ventilation rate for the office to comply with Table 403.3, IMC 2000. |