Permit Number: T04CM01892
Parcel: 127110220

Address:
6046 E 4TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM01892
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2005 GERRY KOZIOL WWM REVIEW Approved
04/04/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T04CM01892

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Floor Plan

1. Identify ceiling heights in all areas on floor plan. If sloped ceiling, note average height.
2. Note and specify that shower enclosures shall have a minimum finished interior area of 1,024 square inches and shall be capable of encompassing a minimum 30" circle per 1994 UPC SEC. 410.0. All glass enclosures shall be tempered.

Structural Plan

1. Shingles or tile roof. Zoning approved plan notes tile roof. Clarify and check with zoning if composite shingles are to be used.
2. 1/4 - Dimension 6" from grade to sill plate.
3. Note and dimension that the fireplace chimney must terminate a minimum of 2' above any point of roof within 10' measured horizontally and not less than 3' above the point where the chimney passes through the roof, per R1001.6. (on elevations)
4. Detail 4/4?

Plumbing and Mechanical Plans

1. Provide pressure and temperature relief valve at water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down. Plumbing notes conflict concerning discharge.
2. Note on plans: Mechanical shall comply with 2003 IRC chapters 13 - 24.

Electrical Plan

1. Provide switch for closet lights.
2. Locate new 200-amp panel and 125-amp subpanel.
3. Clarify loads - Panel 'B' is loaded to 114-amps yet panel 'A' only provides 60-amp breaker and riser diagram shows a 50-amp breaker. Also 114-amps at panel 'B' and 184-amps at panel 'A' is >200-amps which is the limit per new panel main. Also new panel 'A' has circuits that appear to be existing (lighter lines) Clarify.

MODEL ENERGY CODE:

1. Provide energy calculations per the 2000 IECC and comply with IRC chapter 11 or 'Rescheck' that support chosen 'R' and 'U' values.


If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.

NOTE: As of 09/06/04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code. All model plans shall reference these codes.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/05/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
04/05/2005 SUE REEVES REJECT SHELF Completed