| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Note: Use the tables and water fixture unit values from the 1994 UPC. Water piping projects with less than 50 fixture units or less than 200 feet in developed length are to be calculated using Table 6-4. Revise pipe sizes as required. Reference Sections 610.4, 610.12, and 610.13, UPC 1994. |