Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01849
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 06/04/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 06/04/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/04/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Include all fixtures (e.g. hose bibbs) in fixture connection schedule. 2. Water piping projects with less than 50 fixture units or less than 200 feet in developed length are to be calculated using Table 6-4. Revise pipe sizes as required. Reference Sections 610.4, 610.12, and 610.13, UPC 1994. |
| 06/14/2004 | GERRY KOZIOL | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/14/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |