Permit Number: T04CM01849
Parcel: 110055270

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01849
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide plumbing drawings. Permit T04PL00531 was for underground plumbing only.
04/23/2004 ROBERT SHERRY WATER REVIEW Approved
04/23/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information for EF-2.
2. Coordinate the area of the break room in the ventilation calculation with the room size shown on the plans.
3. Modify the required ventilation for AC-1 and AC-2 per Section 403.3.2, IMC 2000.
4. Provide Mechanical energy calculations.
04/27/2004 JIM EGAN FIRE REVIEW Approved
04/27/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
04/28/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
06/04/2004 EGRANT1 WWM REVIEW Needs Review
06/04/2004 EGRANT1 ZONING REVIEW Needs Review
06/04/2004 EGRANT1 ENGINEERING REVIEW Needs Review