Permit Number: T04CM01840
Parcel: 111041760

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM01840
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2004 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Please include a response letter with the next submittal that states how all comments have been addressed.

2. Correct all text/symbol overlays.

3. Indicate sidewalk scupper for roof downspout on northwest entrance of building.

4. Indicate existing sight visibility triangles for PAALs onto Palo Verde Ave.; Near side is 185' and Far side is 110'.

5. On-site curb returns require an 18 foot Radius. Correct and revise entrance curb 6'-6" to 18' R.
09/23/2004 ANDREW CONNOR NPPO REVIEW Denied Submit NPPO plan per DS 2-15.0
09/23/2004 Andrew Connor LANDSCAPE REVIEW Denied 1. One (1) canopy tree must be provided for every thirty-three (33) linear feet of landscape border per LUC 3.7.2.4. Include additional trees within the street landscape borders along Kleindale Rd. to the east and west of ingress and egress.

2. Indicate on the site and landscape plans the type of material (e.g., masonry wall) for screen walls. Curbing is still necessary for the vehicle use area to protect screen walls from vehicular damage revise landscape and site plans to include screen walls and curbing per DS 2-07.2.2.A.3

3. Include note on landscape plan: All landscape areas will be depressed for water harvesting.
10/04/2004 DAN CASTRO HANDICAP-SITE REVIEW Approved
10/04/2004 Daniel Castro ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2004 TAMI ACHONG OUT TO CUSTOMER Completed
10/04/2004 ANGIE SHOFFSTALL REJECT SHELF Completed