Permit Number: T04CM01824
Parcel: 128100530

Review Status: Completed

Review Details: REVISION - WALK THRU

Permit Number - T04CM01824
Review Name: REVISION - WALK THRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM01824 DENIED 8/24/04
1. It appears that Phases A and B are overloaded at 103A and 106A respectively. Please rebalance, or change CB in Panel L#C from 100A to 110A or 125A.