Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied 1. See prior comment #1, complete area calculation portion of code review checklist (1. Provide completed code review checklist.)
2. See prior comment #2, this project is required to address accessibility requirements : 1. show where 20% of project valuation is spent on accessibility (IBC Sec 3408) or 2.showing site and building comply fully with IBC Sec 11 and ANSI A117.1 - 1998 ed. (2. Address accessibility show conformance w/ IBC Sec 11 and ANSI A117.1-1998 ed.
3. See prior comment #3, show fastener type,size,spacing/number. (3. Provide wall details showing connection to structure above and below , including connections of bracing top and bottom.)

Questions, call Douglas Laakso, City of Tucson, Structural Plans Examiner at (520) 791-5550 x 1111.
06/28/2004 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review