Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM01813
Parcel: 12108001B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01813
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2004 JIM EGAN FIRE REVIEW Approved
04/27/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/27/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
04/27/2004 GERRY KOZIOL WWM REVIEW Approved
04/27/2004 DAN CASTRO ZONING REVIEW Approved
04/27/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/27/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM01813 DENIED 4/27/04
1. Clarify Keynote #6, as to what it feeds. Panel, circuit, load. Justify the total of (5) #10 and (2) #10 GND.
2. Provide a disconnect for the water heater per NEC 422 Part C.
3. Water heater 3000 W wold have 3000/208 = 14.4 A. Per NEC 422-11 (e) (3), the overcurrent protection shall not exceed 150% of the rating of the appliance. Next size up from 21.6 A is 25A CB.
04/27/2004 ROBERT SHERRY WATER REVIEW Approved
04/27/2004 BLANCA ESPINO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/03/2004 EGRANT1 OUT TO CUSTOMER Completed