Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01813
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/27/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
04/27/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
04/27/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/27/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
04/27/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
04/27/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/27/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM01813 DENIED 4/27/04 1. Clarify Keynote #6, as to what it feeds. Panel, circuit, load. Justify the total of (5) #10 and (2) #10 GND. 2. Provide a disconnect for the water heater per NEC 422 Part C. 3. Water heater 3000 W wold have 3000/208 = 14.4 A. Per NEC 422-11 (e) (3), the overcurrent protection shall not exceed 150% of the rating of the appliance. Next size up from 21.6 A is 25A CB. |
04/27/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/27/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/03/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |