Permit Number: T04CM01813
Parcel: 12108001B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01813
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/21/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water pressure calculations. Show that the water piping has been sized per Section 610.1, UPC 1994, and does not overload the existing water piping.
2. Show the size of the waste line to which the new fixtures are being connected and the total number of fixture units connected to the existing waste line.
04/21/2004 ROBERT SHERRY WATER REVIEW Approved
04/21/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation calculations and show the balancing information of the drawing.
04/27/2004 EGRANT1 FIRE REVIEW Needs Review
04/27/2004 EGRANT1 WWM REVIEW Needs Review
04/27/2004 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
04/27/2004 EGRANT1 ZONING REVIEW Needs Review
04/27/2004 EGRANT1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/27/2004 EGRANT1 OUT TO CUSTOMER Completed