Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01813
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/21/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water pressure calculations. Show that the water piping has been sized per Section 610.1, UPC 1994, and does not overload the existing water piping. 2. Show the size of the waste line to which the new fixtures are being connected and the total number of fixture units connected to the existing waste line. |
| 04/21/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/21/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation calculations and show the balancing information of the drawing. |
| 04/27/2004 | EGRANT1 | FIRE | REVIEW | Needs Review | |
| 04/27/2004 | EGRANT1 | WWM | REVIEW | Needs Review | |
| 04/27/2004 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/27/2004 | EGRANT1 | ZONING | REVIEW | Needs Review | |
| 04/27/2004 | EGRANT1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/27/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |