Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01785
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/20/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
04/20/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide pan under water heater. |
04/20/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/20/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/20/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the location of the 16x12 SA ducts. Keynote #1 and the sidewall registers mounted on the ducts imply that they are located below the ceiling but notes on the mechanical plan call for them to be located above the ceiling. |
05/13/2004 | LLESNY1 | ZONING | REVIEW | Needs Review | |
05/13/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
05/13/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/13/2004 | LLESNY1 | ENGINEERING | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/13/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |