Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM01762
Parcel: 10511061R

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T04CM01762
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2004 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
05/17/2004 TACHONG1 WWM REVIEW Needs Review
05/17/2004 TACHONG1 WATER REVIEW Needs Review
05/18/2004 WILDAN 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/18/2004 LISA LESNY OUT TO CUSTOMER Completed