Permit Number: T04CM01762
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01762
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
04/16/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
04/19/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide access and working space for the water heater. Reference Section 511.2, UPC 1994.
2. Provide description of the "Open Site Drain" . Reference Sections 301.1.1 and 804.1, UPC 1994.
3. The "Open Site Drain" may not be located above the ceiling. Reference Section 804.1, UPC 1994.
4. Provide calculations to show that the water supply piping has been sized in accordance with Section 610.0, UPC 1994.
5. Show the size of the water supply pipe to which the new plumbing fixtures are being connected.
6. Drawing note #8 indicates that the T&P relief line is to be terminated over the mop sink (in conflict with drawing note 13 and domestic water riser diagram). The mop sink is not an approved termination point for the T&P relief. Reference Section 608.5, UPC 1994.
7. Show how the new drainage piping is coordinated with the existing drainage piping. Reference Section 103.2.3, UPC 1994.
8. The new floor cleanout does not provide adequate service for the drain pipe from the mop sink. Install cleanout for the mop sink. Reference Section 707.4, UPC 1994.
04/19/2004 NEAL SAUNDERS BUILDING-COMMERCIAL REVIEW Needs Review
04/19/2004 EGRANT1 WWM REVIEW Needs Review
04/19/2004 JIM EGAN FIRE REVIEW Approved
04/19/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/19/2004 EGRANT1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/19/2004 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/17/2004 TAMI ACHONG OUT TO CUSTOMER Completed