Permit Number: T04CM01750
Parcel: 107130030

Address:
2707 N 1ST AV

Review Status: Completed

Review Details: SITE

Permit Number - T04CM01750
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2004 Andrew Connor LANDSCAPE REVIEW Denied Screens or walls whether required or not, are to be located on the development side of the street landscape border so that the landscaping is visible from the street per DS 2-06.3.7.B.2. The wall indicated in keynote #25 on the site plan appears to be located in front landscaping along 1st Ave.
08/02/2004 Andrew Connor NPPO REVIEW Approved
08/03/2004 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Please include a response letter with the next submittal that states how all comments have been addressed. Include plans/redlines from previous plan submittal.

2. All lettering and dimensions shall be the equivalent of twelve (0.12") point or greater in size. The purpose of this requirement is to assure that all lettering is legible when reviewed and will maintain that legibility when reproduced and photographically reduced (microfilmed) for record-keeping purposes. D.S. 2-05.2.1.C

3. Indicate contour intervals along with the north arrow and scale. This should be placed together on the Site Plan. D.S. 2-02.2.1.A.1

4. Indicate property description. D.S. 2-02.2.1.A.2

5. Indicate location map on Site Plan. D.S. 2-02.2.1.A.4

6. Indicate all existing buildings and structures, including roof slope and location of downspouts. D.S. 2-02.2.1.A.6 Add note: "All roof spouts will be routed under any adjacent sidewalk". Sidewalks shall be flood free for all storm discharges of up to a ten (10) year flood event. Indicate roof direction & lot drainage. D.S. 2-08.3.1 & 4.1.E

7. Indicate and label all existing and future (widening) sight visibility triangles. D.S. 2-02.2.1.A.10

8. Clearly identified vehicular and pedestrian circulation. The minimum acceptable width for
two-way paved roadway is 24'. Show dimension for driveway on First Ave.. D.S. 2-02.2.1.A.12

9. Indicate type, size and height of existing signage. As per Keynote #36 existing sign to remain is not acceptable. Relocate sign in an area that is outside of existing and future SVT's. D.S. 2-02.2.1.A.13

10. Dimension and demonstrate maneuvering area for loading space(s). D.S. 2-02.2.1.A.14


11. Indicate drainage patterns, proposed finish floor elevation(s) and finish grades. Do not obstruct offsite to onsite flows. D.S. 2-02.2.1.A.16

12. Indicate estimated cut and fill quantities. D.S. 2-02.2.1.A.17

13. Indicate if street is Public or Private. 1st Ave. is a MS&R street with future right-of-way of 120 feet, which intersects with Glenn St. requiring a widening of 150 feet by 300 feet tapering to 120 feet by another 300 feet. Show adjacent driveways. D.S. 2-02.2.1.A.18

14. Dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way. Indicate existing, future (widening) widths. D.S. 2-02.2.1.A.19

15. If applicable, indicate all easements of record to be graphically shown on the plan together with recording docket and page reference. D.S. 2-02.2.1.A.20

16. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways and utility lines. Indicate utilities with a light line weight. Gas utility line is blurry. Correct and revise. D.S. 2-02.2.1.A.21

17. Indicate existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. D.S. 2-02.2.1.A.23 Indicate contour symbol in legend.

18. Demonstrate vehicle maneuverability fully dimensioned. The maximum back-up distance for the collection vehicle shall be forty (40) feet. D.S. 6-01.4.1.C Indicate a refuse enclosure detail as per D.S. 6-01.4.2
08/04/2004 TACHONG1 ZONING REVIEW Needs Review
08/04/2004 TACHONG1 HANDICAP-SITE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2004 TAMI ACHONG OUT TO CUSTOMER Completed