Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01678
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/13/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
04/13/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
04/13/2004 | LINDA BUCZYNSKI | BUILDING-COMMERCIAL | REVIEW | Denied | T04CM01678 DENIED 4/13/04 1. If any lighting and receptacle work on this project is to be relocated from existing, state so on the plans, specific to each fixture/outlet. 2. Provide panel and circuit numbers for any lights or receptacles which are new. 3. If existing circuitry is to be used with no load changes, state so on the plans. 4. Document any load changes with load calculations. |
04/13/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/13/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
04/13/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/13/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
05/06/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
05/06/2004 | LLESNY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/06/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |