Permit Number: T04CM01655
Parcel: 105102410

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01655
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2004 JIM TATE ENGINEERING REVIEW Approved
04/12/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide decription of plumbing fixtures. Reference Sections 401.1 and 410.1, UPC 1994.
2. Provide fixture unit tabulation and water pressure calculations to show that the piping has been sized in accordance with Section 610, UPC 1994.
3. Provide protection for trap seals of floor drains and similar traps. Reference Section 1007.0 UPC 1994 with State of Arizona amendments.
4. Revise connection of disposals to sanitary system, Reference Section 1001.3, UPC 1994.
5. Revise drains from sinks with hair interceptors. Reference Section 1001.1, UPC 1994.
6. Provide vent for FS-2 located under dry tank display. Reference Section 901.0, UPC 1994.
04/12/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
04/12/2004 ROBERT SHERRY WATER REVIEW Approved
04/12/2004 JIM EGAN FIRE REVIEW Approved
04/12/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. In-duct smoke detectors are to be located in the return duct, not the supply duct.
04/15/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Provide a.i.c. at service as well as at panels. Indicate the panels withstand rating. 2. Add 125% to all continuous loads and re calculatr loads.
04/19/2004 TACHONG1 WWM REVIEW Needs Review
04/19/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied Incomplete submittal

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2004 TAMI ACHONG OUT TO CUSTOMER Completed