Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01655
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 04/12/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide decription of plumbing fixtures. Reference Sections 401.1 and 410.1, UPC 1994. 2. Provide fixture unit tabulation and water pressure calculations to show that the piping has been sized in accordance with Section 610, UPC 1994. 3. Provide protection for trap seals of floor drains and similar traps. Reference Section 1007.0 UPC 1994 with State of Arizona amendments. 4. Revise connection of disposals to sanitary system, Reference Section 1001.3, UPC 1994. 5. Revise drains from sinks with hair interceptors. Reference Section 1001.1, UPC 1994. 6. Provide vent for FS-2 located under dry tank display. Reference Section 901.0, UPC 1994. |
| 04/12/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/12/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/12/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/12/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. In-duct smoke detectors are to be located in the return duct, not the supply duct. |
| 04/15/2004 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide a.i.c. at service as well as at panels. Indicate the panels withstand rating. 2. Add 125% to all continuous loads and re calculatr loads. |
| 04/19/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 04/19/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | Incomplete submittal |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/19/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |