Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01653
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/09/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
04/12/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/12/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
04/13/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water calculations. Include the existing fixtures being served by the same water meter in the water calculations. Revise water pipe sizing as required. Reference Section 610.1, UPC 1994. 2. Show that the distribution of cleanouts in the revised building drain (existing plus new) meets the requirements of Section 707.4, UPC 1994. |
04/13/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM01653 DENIED 4/13/04 1. Provide fused disconnects for VAVs per Sheet M1. Indicate fuse sizes. 2. It appears that Ckt LIG-26 on power plan is actually LIG-42. 3. Provide load calculations for Panel LD-2, HD-2, and the main. |
04/13/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/13/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise ventilation calculations to comply with Section 403.3.2, IMC 2000. 2. Provide fire/smoke dampers at penetrations of exit corridor wall. Reference Section 607.5, IMC 2000. |
04/20/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | |
04/29/2004 | TACHONG1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/29/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |