Permit Number: T04CM01653
Parcel: 116193740

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01653
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2004 JIM TATE ENGINEERING REVIEW Approved
04/12/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
04/12/2004 JIM EGAN FIRE REVIEW Approved
04/13/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water calculations. Include the existing fixtures being served by the same water meter in the water calculations. Revise water pipe sizing as required. Reference Section 610.1, UPC 1994.
2. Show that the distribution of cleanouts in the revised building drain (existing plus new) meets the requirements of Section 707.4, UPC 1994.
04/13/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM01653 DENIED 4/13/04
1. Provide fused disconnects for VAVs per Sheet M1. Indicate fuse sizes.
2. It appears that Ckt LIG-26 on power plan is actually LIG-42.
3. Provide load calculations for Panel LD-2, HD-2, and the main.
04/13/2004 ROBERT SHERRY WATER REVIEW Approved
04/13/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise ventilation calculations to comply with Section 403.3.2, IMC 2000.
2. Provide fire/smoke dampers at penetrations of exit corridor wall. Reference Section 607.5, IMC 2000.
04/20/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied
04/29/2004 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2004 TAMI ACHONG OUT TO CUSTOMER Completed