Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T04CM01640
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/27/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 05/11/2004 | Terry Stevens | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T04CM01640 5/11/04 PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. GENERAL REQUIREMENTS: 1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. SITE PLAN: 1. FOR EXISTING STRUCTURE--------INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND WHERE THEY ENTER THE BUILDING. FOUNDATION PLANS: 1. NOTE AND DETAIL MINIMUM REINFORCING, OR PROVIDE CODE JUSTIFICATION OF ALTERNATE: MISSING AT DETAILS 4,4B,AND 3 OF PAGE 1 2. LOCATE AND DETAIL ALL FOOTINGS FOR THE FOLLOWING: - INTERIOR BEARING WALLS----NEW AND EXISTING FLOOR PLANS: 1. ALL WINDOWS WITHIN A 24" ARC OF EITHER VERTICAL EDGE OF A DOOR SHALL BE SAFETY GLASS. UBC SEC 2406.-------------AT INTERIOR WALL 2. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2 3. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT. STRUCTURAL PLANS: 1. PROVIDE COMPLETE ROOF FRAMING PLANS. SHOW SIZE, SPACING AND SPAN OF ALL FRAMING MEMBERS, RAFTERS, BEAMS, LINTELS, HEADERS, LEDGERS AND BLOCKING. 2. LCC4.5-4 POST CAP HAS NO UPLIFT VALUES AND IS FOR 3-2X10 NOT 1- 4X10 3. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING PLANS: - LEDGERS TO MASONRY -----LEDGER IS REQUIRED IN ORDER TO COMPLETE EDGE NAILING FOR ROOF DIAPHRAM------WP HANGER DOES NOT MEET THIS REQUIREMENT. DETAIL CONNECTION OF RAFTER PARALLEL TO MASONRY WALL ALSO. - JOIST TO LEDGER - HANGER TYPES - BOND BEAMS-------IN NEW AND EXISTING MASONRY 4. 4X8@48"OC ARE INADEQUATE FOR 16'-6" SPAN ----CHANGE OR SUBMIT CALCS. 5. NOTE AND DETAIL TIE STRAPS FRAMING ANCHORS AND JOIST HANGERS BY TYPE, SIZE AND REQUIRED ATTACHMENT TO FRAMING MEMBERS. 6. IS 4-2X10 HEADER AT INTERIOR WALL CLEAR SPANNING 20' OR ARE POSTS BEING USED. CLEARLY INDICATE ON ROOF FRAMING PLAN 7. INDICATE LINTELS FOR ALL OPENINGS IN MASONRY WALLS. SECTIONS - DETAILS - MISC. NOTES: 1. NOTE AND SPECIFY THE SIZE, SPACING AND LENGTH OF ANCHOR BOLTS FOR ALL TOP PLATES AND LEDGERS. 2. NOTE AND SPECIFY ALL LEDGERS AND CONNECTIONS TO WOOD, FRAME OR MASONRY. PLUMBING PLANS: 1. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH SEE NOTE#5 2. PROVIDE SIZE AND LOCATION OF ALL WATER LINES. 3. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWERHEADS 3 GALLONS PER MINUTE. 4. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. 5. THE CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE. ELECTRICAL PLANS: 1. NOTE THE GROUNDING AND BONDING METHOD FOR SUBPANEL. PLAN INDICATES NEW SERVICE -----CLARIFY IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: TERRY STEVENS @ 791-5550 EXT. 1112 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/13/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |
| 05/12/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |