Permit Number: T04CM01635
Parcel: 11806103A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM01635
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2004 GERRY KOZIOL WWM REVIEW Denied need 8th floor wastewater review
07/29/2004 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM01635

7/29/04 1989 W. SAN JUAN TRL. #2

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.
2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FOUNDATION PLANS:

1. SIMPSON DOESN'T LIST A PAHD22. HPAHD22 ?

2. PLEASE SIZE THE FOOTING WIDTHS FOR ONE-STORY, PER TABLE R403.1 . ( 16" MINIMUM; WOOD FRAME )

FLOOR PLANS:

1. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

2. COMPLY WITH R309.2. PROVIDE ½" GYPSUM BOARD ON ALL WALLS COMMON TO THE GARAGE AND HOUSE.
NOTE DOORS BETWEEN HOUSE AND THE GARAGE SHALL BE MINIMUM 1-3/8" SOLID CORE, PER R309.1

3. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2

4. APPLIANCES INSTALLED IN GARAGES SHALL BE MOUNTED ON PLATFORMS AT LEAST 18" ABOVE THE
FLOOR, PER M1307.3

STRUCTURAL PLANS:

1. 2 - 2 X 8 #2 D.F. APPEARS TO BE INADEQUATE FOR A 6' SPAN. (6040)

2. 2 - 2 X 6 #2 D.F. APPEARS TO BE INADEQUATE FOR A 4' SPAN. (4040)

3. SPECIFY LUMBER GRADE AND SPECIES.




4. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

5. DETAIL GABLE END BRACING CONNECTIONS.

7. SPECIFY THE SPACING OF THE 2 X 6 RAFTERS OVER FRAMING THE TRUSSES AND PROVIDE A PLATE OR JUSTIFY A POINT LOAD ON THE ROOF DECK.

ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

2. FOAM INSULATION: CLARIFY YOUR COMPLIANCE WITH R318 FOR THE WALLS TO THE ATTIC PER R318.2.3.

SECTIONS - DETAILS - MISC. NOTES:

1. 3 / 4 ; DIMENSION THE FOOTING'S WIDTH.

PLUMBING PLANS:

1. SIZE THE GAS LINES.

2. PROVIDE VENTS FOR THE DRAINS AND WASTES.

3. ¾" WATER DISTRIBUTION APPEARS INADEQUATE BETWEEN THE WATER HEATER AND THE MASTER BATH.

MECHANICAL PLANS:

1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC.

2. CLARIFY THE "HI / LOW VENTING……." FOR THE FURNACE AND WATER HEATER. SHOULD THE VENTS BE IN THE GARAGE WALLS ? ARE THE APPLIANCES WALLED IN ? PLEASE SIZE THE VENTS. SEE U.P.C. TABLE 5 - 1 AS AMENDED BY THE STATE. THE STATE AMENDMENTS ARE ON THE CITY WEB-SITE WWW.CITYOFTUCSON.ORG .

3. PROVIDE THE SIZE AND LOCATION OF THE RETURN AIR. SEE M1602 .

4. SIZE THE SUPPLY AIR TO THE FIRST DUCT TAP. SEE M1603 .

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. DESIGNATE THE LOCATION AND CIRCUIT OF ALL REQUIRED LIGHT FIXTURES, RECEPTACLE OUTLETS, POWER
OUTLETS AND SWITCHES. ( ASSIGN A CIRCUIT TO EACH ELECTRICAL DEVICE ON THE FLOOR PLAN )

3. RECEPTACLES AT THE KITCHEN COUNTER TOPS ARE REQUIRED TO BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24" FROM A RECEPTACLE OUTLET, PER E3801.4.1

4. ALL READILY ACCESSIBLE RECEPTACLE OUTLETS IN GARAGES ARE REQUIRED TO HAVE GROUND FAULT CIRCUIT INTERRUPTING PROTECTION. NOTE ON THE DRAWINGS AT EACH OUTLET REQUIRING SUCH PROTECTION. SEE E3802.

5. A RECEPTACLE IS REQUIRED IN THE SOUTH EAST CORNER OF THE LIVING ROOM.

6. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

7. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.