Permit Number: T04CM01625
Parcel: 10819008G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01625
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/08/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculation to show that the water piping has been sized in compliance with Section 610.0, UPC 1994. Include effect of existing fixtures conected to the water meter serving this address.
2. Provide riser diagram for the water supply piping. Reference Section 103.2.3, UPC 1994.
3. Provide legible registrant's seal.
04/08/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
04/08/2004 ROBERT SHERRY WATER REVIEW Approved
04/08/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/12/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM01625 DENIED 4/12/04
HP on LG-32,34,36 is not on panel schedule, not on mechanical drawings. Please clarify/correct as necessary.
04/12/2004 JIM EGAN FIRE REVIEW Approved
04/19/2004 CAGUILA1 WWM REVIEW Needs Review
04/19/2004 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review