Permit Number: T04CM01618
Parcel: 112050530

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM01618
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE STRUCTURAL CALCULATIONS AND NEW ROOF RAMING PLAN FOR REVISED LOCATION OF MECHANICAL UNITS.
2) CLARIFY ON STRUCTURAL AND PLUMBING DRAWINGS INTENT OF WALL ENCLOSURE FOR RESTROOM FACILITIES.
12/01/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide an updated roof framing plan (with structural calcs) showing the revised locations of the A/C units.
12/01/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the intent of the revision: sheet A2.0 appears to show the restrooms being deleted from the project but sheet P1.0 still shows the water closets and lavs being installed.
12/13/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Electrical revisions are technically correct and Code-compliant. Electrical Plans Examiner will approve such revisions after Mechanical and Building revisions as reflected in the revised electrical drawings, have been approved.