Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/13/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Coordinate the ventilation calculations with the designated uses of the spaces in the building. Show how each A/C unit is providing the correct amount of outside air to the spaces it serves (e.g. HP-13 serves the conference room, breakroom, and part of the open office.).
04/15/2004 LLESNY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2004 LISA LESNY OUT TO CUSTOMER Completed