Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01616
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/07/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
04/07/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Correct water pressure calculations. 2. Correct fixture unit calculations: K.S. w/ dishwasher = 4 water F.U./ 3 waste F.U.; Water closet = 6 waste F.U. 3. Provide cut sheet for air compressor showing that the condensate is oil-free or provide oil-water separator. |
04/07/2004 | NEAL SAUNDERS | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/07/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
04/07/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/07/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the ventilation calculations with the designated uses of the spaces in the building - its not all office space. 2. Clarify the amount of outside air to be provided to the space - the equipment schedule calls out 25% outside air for all of the units but the ventilation note calls for 3 of the units to supply 280 cfm. |
04/07/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
04/07/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/07/2004 | JIM TATE | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/07/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |