Permit Number: T04CM01616
Parcel: 108192420

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01616
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2004 JIM EGAN FIRE REVIEW Approved
04/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct water pressure calculations.
2. Correct fixture unit calculations: K.S. w/ dishwasher = 4 water F.U./ 3 waste F.U.; Water closet = 6 waste F.U.
3. Provide cut sheet for air compressor showing that the condensate is oil-free or provide oil-water separator.
04/07/2004 NEAL SAUNDERS BUILDING-COMMERCIAL REVIEW Approved
04/07/2004 TACHONG1 WWM REVIEW Needs Review
04/07/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
04/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the ventilation calculations with the designated uses of the spaces in the building - its not all office space.
2. Clarify the amount of outside air to be provided to the space - the equipment schedule calls out 25% outside air for all of the units but the ventilation note calls for 3 of the units to supply 280 cfm.
04/07/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/07/2004 ROBERT SHERRY WATER REVIEW Approved
04/07/2004 JIM TATE ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2004 TAMI ACHONG OUT TO CUSTOMER Completed