Permit Number: T04CM01613
Parcel: 13409018C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01613
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Specify the type of backflow preventers to be used on the water supplies to the pedicures.
2. The pumped discharge from the pedicures does not require a vent and if one is to be installed, it may not be connected to a sanitary vent.
05/05/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The ventilation for the project appears to be provided by a single rooftop air conditioner. Provide sufficient information to show that the quantity of ventilation air meets the requirements of section 403.3.2, IMC 2000.
05/12/2004 LLESNY1 WWM REVIEW Needs Review
05/12/2004 LLESNY1 BUILDING-COMMERCIAL REVIEW Needs Review
05/12/2004 LLESNY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2004 LISA LESNY OUT TO CUSTOMER Completed