Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/05/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Specify the type of backflow preventers to be used on the water supplies to the pedicures. 2. The pumped discharge from the pedicures does not require a vent and if one is to be installed, it may not be connected to a sanitary vent. |
05/05/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The ventilation for the project appears to be provided by a single rooftop air conditioner. Provide sufficient information to show that the quantity of ventilation air meets the requirements of section 403.3.2, IMC 2000. |
05/12/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
05/12/2004 | LLESNY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
05/12/2004 | LLESNY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |