Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM01613
Parcel: 13409018C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01613
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2004 JIM EGAN FIRE REVIEW Approved
04/15/2004 ROBERT SHERRY WATER REVIEW Approved
04/15/2004 LLESNY1 BUILDING-COMMERCIAL REVIEW Denied
04/15/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/15/2004 DAN CASTRO ZONING REVIEW Approved
04/15/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation conforming to the requirements of Section 403.3, IMC 2000.
04/15/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide reduced pressure backflow preventers to each hot and cold water outlet for the whirlpool spas. Reference Section 603.0, UPC 1994.
2. Provide indirect waste receptor for the discharge of the whirlpool spas. Reference Section 805.0, UPC 1994.
04/15/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied DENIED 4/15/04 T04CM01613
GFCI protect foot spa receptacles or circuit.
05/05/2004 SREEVES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2004 SUE REEVES OUT TO CUSTOMER Completed