Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01613
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/15/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
04/15/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/15/2004 | LLESNY1 | BUILDING-COMMERCIAL | REVIEW | Denied | |
04/15/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
04/15/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
04/15/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation conforming to the requirements of Section 403.3, IMC 2000. |
04/15/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide reduced pressure backflow preventers to each hot and cold water outlet for the whirlpool spas. Reference Section 603.0, UPC 1994. 2. Provide indirect waste receptor for the discharge of the whirlpool spas. Reference Section 805.0, UPC 1994. |
04/15/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | DENIED 4/15/04 T04CM01613 GFCI protect foot spa receptacles or circuit. |
05/05/2004 | SREEVES1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/05/2004 | SUE REEVES | OUT TO CUSTOMER | Completed |