Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM01596
Parcel: 123150800

Review Status: Completed

Review Details: REVISION - WALK THRU

Permit Number - T04CM01596
Review Name: REVISION - WALK THRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2004 DAVE WITT BUILDING-RESIDENTIAL REVIEW Approved