Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM01575
Parcel: 137340010

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM01575
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM01575 DENIED 6/11/04

1. WH-1 is 4500 W on Sheet A 2, and totals 16,680 on electrical panel. Please clarify.
2. Keynote 5 calls for a 20/3 breaker. The 3-P breaker on the panel is 40A. Please clarify.
3. Keynote 7 calls for a duplex outlet for a sump pump. The only duplex outlet shown in the area is going to Ckt 21, which powers the WH. Please clarify.
4. Ckt A 25 powers a GFCI outlet on the plans. On the panel schedule 25 is one of the three poles in the WH CB.
5. Provide a disconnect for REF-1 per NEC 430-109.
6. Ckt A 23 powers something on the roof. On the panel schedule 23 is one of the three poles in the WH CB.

The Code of the State Board of Technical Registration ARTICLE 3. REGULATORY PROVISIONS. 32-143 Exceptions, states:
A registrant under this chapter may engage in practice in another category regulated pursuant to this chapter only to the extent that the person is qualified and to the extent that the work may be necessary and incidental to the work of the registrant's profession on a specific project. This exception does not apply to public works projects.

Based upon my review and in accordance with the State Board of Technical Registration Rules, this plan should be designed and sealed by an Arizona registered professional electrical engineer.
06/11/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/11/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show details for the installation of the foot
spas. A reduced pressure backflow preventer will be required for the hot and cold water supplies for eash foot spa. Show how the foot spas are to be connected to the sanitary waste
system. Show how the reduced pressure backflow preventers are to be drained. Reference Section
103.2.3, UPC 1994.
2. Termination of the T&P relief for the water
heater shall conform to the requirements of Section
608.5, UPC 1994.
3. Show how the sanitary waste piping is coordinated
with the existing building drains.
06/29/2004 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
06/29/2004 EGRANT1 WWM REVIEW Needs Review