Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM01575
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/10/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show details for the installation of the foot spas. (Sheet A15 is referenced but has not been included.) A reduced pressure backflow preventer will be required for the hot and cold water supplies for eash foot spa. Show how the foot spas are to be connected to the sanitary waste system. Reference Section 103.2.3, UPC 1994. 2. Clarify which of the three water heater details is to be used. 3. Termination of the T&P relief for the water heater shall conform to the requirements of Section 608.5, UPC 1994. 4. Show how the sanitary waste piping is coordinated with the existing building drains. |
05/10/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations showing that the ventilation for the tenant space complies with Section 403, IMC 2000. The occupant load for this space is 25 persons per 1000 square feet. Reference Section 403.3, IMC 2000. 2. Provide balancing data along with listing information (Manufacturer, model number, HP, etc.) for the proposed exhaust fan. Show this data on the drawings. |
05/10/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | DENIED 5/10/04 T04CM01575 1. Water heater is 3-phase on Sheet A-2, but only on Circuit 21 on Panel Schedule. Please clarify. 2. Provide loading for Circuits 21, 23, and 25 on the Panel Schedule. 3. Notes 1, 2 and 5 provide for power from the nearest panel. Exact panel and circuit should be specified, and appears to be elsewhere. Please eliminate the confusing wording. 4. Provide power requirements for REF-1. 5. REF-1 is most likely hard wired. Clarify the use of the WP GFI receptacle. |
06/11/2004 | EGRANT1 | WWM | REVIEW | Needs Review | |
06/11/2004 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/11/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |