Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show details for the installation of the foot
spas. (Sheet A15 is referenced but has not been included.) A reduced pressure backflow preventer will be required for the hot and cold water supplies for eash foot spa. Show how the foot spas are to be connected to the sanitary waste
system. Reference Section
103.2.3, UPC 1994.
2. Clarify which of the three water heater details
is to be used.
3. Termination of the T&P relief for the water
heater shall conform to the requirements of Section
608.5, UPC 1994.
4. Show how the sanitary waste piping is coordinated
with the existing building drains.
05/10/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations showing that the ventilation
for the tenant space complies with Section 403,
IMC 2000. The occupant load for this space is 25 persons per 1000 square feet. Reference Section 403.3, IMC 2000.
2. Provide balancing data along with listing information
(Manufacturer, model number, HP, etc.) for the
proposed exhaust fan. Show this data on the drawings.
05/10/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied DENIED 5/10/04 T04CM01575
1. Water heater is 3-phase on Sheet A-2, but only on Circuit 21 on Panel Schedule. Please clarify.
2. Provide loading for Circuits 21, 23, and 25 on the Panel Schedule.
3. Notes 1, 2 and 5 provide for power from the nearest panel. Exact panel and circuit should be specified, and appears to be elsewhere. Please eliminate the confusing wording.
4. Provide power requirements for REF-1.
5. REF-1 is most likely hard wired. Clarify the use of the WP GFI receptacle.
06/11/2004 EGRANT1 WWM REVIEW Needs Review
06/11/2004 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2004 EGRANT1 OUT TO CUSTOMER Completed