Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM01575
Parcel: 137340010

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01575
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
04/05/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
04/06/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. All work shall comply with the requirements of the 1994 edition of the Uniform Plumbing Code, with State of Arizona amendments.
2. Provide calculations to show how the water piping has been sized. Reference Section 610.0, UPC 1994.
3. Show details for the installation of the foot spas. The spas must be listed and if they do not come equipped with backflow protection, either a double check valve or a pressure vacuum breaker must be installed for the hot and cold water supplies for eash foot spa. Show how the foot spas are to be connected to the sanitary waste system; Detail 3/A13 is not an approved indirect waste receptor for a foot spa. Reference Section 103.2.3, UPC 1994.
4. "Hub drains" must be listed and comply with the requirements of Section 410.1, UPC 1994.
5. Clarify which of the three water heater details is to be used.
6. Termination of the T&P relief for the water heater shall conform to the requirements of Section 608.5, UPC 1994.
7. Show how the sanitary waste piping is coordinated with the existing building drains.
8. The minimum acceptable font size for drawings is 10 points.
9. Sheet A15 is referenced but has not been included.
04/06/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM01575 DENIED 4/6/04
1. Provide an Electrical Plan showing location of all equipment, and panel and circuit number.
2. Provide panel schedule and load calculations, and show location of panel on plans.
3. Demonstrate compliance with National Electrical Code. For example, the water heater shall have a disconnect per NEC 422 Part C.
4. Provide specifications for such items as conduit, conductor, installed equipment.
5. See the attached Electrical Permit Requirements sheet.
04/06/2004 ROBERT SHERRY WATER REVIEW Approved
04/06/2004 JIM EGAN FIRE REVIEW Approved
04/06/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations showing that the ventilation for the tenant space complies with Section 403, IMC 2000.
2. Provide balancing data along with listing information (Manufacturer, model number, HP, etc.) for the proposed exhaust fan.
05/10/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review
05/10/2004 GERRY KOZIOL WWM REVIEW Denied clarify all plumbing drawings

Final Status

Task End Date Reviewer's Name Type of Review Description
05/10/2004 TAMI ACHONG OUT TO CUSTOMER Completed