Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM01534
Parcel: 11714220A

Address:
535 S RUSSELL AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T04CM01534
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
04/02/2004 PETER MCLAUGHLIN NPPO REVIEW Passed
04/02/2004 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Needs Review PLAN CHECK COMMENTS - PROJECT #T04CM01534

5/6/04 535 S. RUSSELL AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.
2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM
IF IT EXISTS.

FLOOR PLANS:

1. PROVIDE HANDRAILS AT THE STEPS. SEE R315 .

2. NOTE OR PROVIDE GUARDS AT FLOORS THAT ARE OVER 30" ABOVE GRADE. SEE R316 .

STRUCTURAL PLANS:

1. COLLARS ARE REQUIRED TO BE NOT MORE THAN 4' O.C. SEE R802.3.1 .

2. THE RIDGE BOARD IS REQUIRED TO COVER THE RAFTER'S PLUMB CUT. SEE R802.3 .

3. SPECIFY THE HIP RAFTER OVER THE EXISTING STORAGE ROOM.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
04/02/2004 JIM TATE ENGINEERING REVIEW Approved