Permit Number: T04CM01529
Parcel: 140420200

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01529
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
04/02/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
04/05/2004 GERRY KOZIOL WWM REVIEW Approved
04/08/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/08/2004 ROBERT SHERRY WATER REVIEW Approved
04/08/2004 NEAL SAUNDERS BUILDING-COMMERCIAL REVIEW Needs Review
04/08/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the condensate drain for HP-1 so that the termination point is in the space controlled by tenant of Suite 101. Reference Section 807.2, UPC 1994.
04/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM01529 DENIED 4/5/04
1. Clarify how overload protection is to be provided for CU-1.
04/08/2004 JIM EGAN FIRE REVIEW Approv-Cond Verfication must be provided to indicate that existing fire sprinkler system design is adequate to protect Rack Storage of Class 3 Commodity to 20 feet storage height prior to storage racks being installed.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2004 TAMI ACHONG OUT TO CUSTOMER Completed