Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM01529
Parcel: 140420200

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01529
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
04/02/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
04/05/2004 GERRY KOZIOL WWM REVIEW Approved
04/08/2004 NEAL SAUNDERS BUILDING-COMMERCIAL REVIEW Needs Review
04/08/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/08/2004 JIM EGAN FIRE REVIEW Approv-Cond Verfication must be provided to indicate that existing fire sprinkler system design is adequate to protect Rack Storage of Class 3 Commodity to 20 feet storage height prior to storage racks being installed.
04/08/2004 ROBERT SHERRY WATER REVIEW Approved
04/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM01529 DENIED 4/5/04
1. Clarify how overload protection is to be provided for CU-1.
04/08/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the condensate drain for HP-1 so that the termination point is in the space controlled by tenant of Suite 101. Reference Section 807.2, UPC 1994.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2004 TAMI ACHONG OUT TO CUSTOMER Completed